EEF1

Control EEPROM Error

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

What does EEF1 mean?

A detected error within the Control EEPROM. This non-volatile memory stores critical drive parameters and firmware. Corruption here can prevent the drive from booting, operating, or retaining its configuration, leading to a complete system failure.

Common Causes

  • Data corruption within the EEPROM due to power disturbances (e.g., voltage spikes, brownouts, unstable supply).
  • Failed EEPROM chip on the control board, preventing reliable read/write operations of stored parameters.
  • Firmware update process interrupted or failed, leaving the EEPROM in an inconsistent or partially written state.
  • Electrostatic discharge (ESD) damage to the control board during handling or maintenance activities.
  • Over-temperature condition in the drive's control section, leading to component stress and memory degradation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power cycle the drive. If the fault persists, attempt a factory reset (e.g., set Parameter P0-01 = 2) to re-initialize EEPROM content.

  2. 2

    2. Re-load a known-good configuration file via the drive's communication port to overwrite potentially corrupted data.

  3. 3

    3. Verify the stability of the drive's internal control power supply (e.g., 24VDC rail) using a multimeter.

  4. 4

    4. Check the drive's ambient operating temperature and ensure cooling fans are functioning correctly (e.g., fan current, airflow).

  5. 5

    5. If persistent, consider replacing the control board as the EEPROM chip may be physically damaged or worn out.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026