Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
A hardware detected error, specifically related to IGBT desaturation. This indicates a very high voltage drop across an IGBT, often due to a short circuit in the motor or power wiring, or an internal IGBT failure. This is a critical fault that can lead to immediate hardware damage if not addressed.
Click steps to track your progress.
Immediately inspect motor wiring and connections for any signs of short circuits to ground or phase-to-phase.
Measure insulation resistance of the motor phases to ground and between phases using a megger (expect >1 MΩ).
Check the drive's output terminals for signs of arcing, carbon buildup, or damage.
If external wiring is verified clear, the drive's power section (IGBTs) may be damaged and require replacement.