Indicates that the motor's thermal model in the drive has calculated an overload condition, suggesting the motor is operating too hot. This protection mechanism prevents motor winding damage due to excessive current over time. The fault typically clears after the motor has cooled down.
Click steps to track your progress.
Measure the motor's operating current (U, V, W) during normal operation and compare to its nameplate rated current; ensure it's not consistently exceeding rated.
Verify all motor nameplate parameters (P1-01 to P1-05) are accurately programmed into the drive's motor data settings.
Inspect the motor's cooling fan for proper operation and clean any dust or debris from its housing or cooling fins.
Check the ambient temperature at the motor's location; reduce if it consistently exceeds motor specification (e.g., > 40°C).
Monitor the motor's calculated thermal state (e.g., parameter d0-08 "Motor Thermal State") and compare it to the trip threshold (e.g., 100%).