Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
A hard detection of a load short-circuit during the Igon load sequence. This implies a short circuit condition was detected at the motor output during the drive's internal initialization or measurement sequence, indicating a problem with the motor or its wiring before full operation.
Click steps to track your progress.
1. Disconnect the motor cables from the drive's output terminals (U, V, W).
2. Use a megohmmeter to measure insulation resistance between motor phases and from each phase to ground (PE) with the motor cold.
3. Use a low-resistance ohmmeter to measure winding resistance between motor phases (U-V, V-W, W-U); compare to nameplate data.
4. Power up the drive with no motor connected and verify it clears the SCF5 fault.
5. Review drive parameters (e.g., P0-01 to P0-10) for correct motor type, voltage, current, and frequency settings.