EL
ErrorLib
Brands
||
  1. Home
  2. Schneider Electric
  3. Altivar Machine ATV320 Variable Speed Drive
  4. SLF1
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

SLF1

Modbus Local Serial Communication Interruption

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

What does SLF1 mean?

An interruption in Modbus local serial communication. This means the drive has lost communication with its Modbus master or other devices on the local serial network, preventing remote control, monitoring, or data exchange. This can lead to a loss of process control.

Common Causes

  • Broken or disconnected RS-485 communication cable (e.g., twisted pair to terminals A+, B-).
  • Incorrect Modbus communication parameters (e.g., baud rate, parity, slave address, P1-30, P1-31).
  • Termination resistor (120 Ohm) missing or incorrectly placed on the Modbus network.
  • Faulty Modbus master device or interference on the communication bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify physical cable connections to the drive's RS-485 terminals (e.g., A+, B-, GND) for secure contact.

  2. 2

    2. Check Modbus communication parameters in the drive (e.g., P1-30 for address, P1-31 for baud rate) and ensure they match the master.

  3. 3

    3. Use a Modbus analyzer or oscilloscope to check signal integrity on the RS-485 bus at the drive terminals.

  4. 4

    4. Confirm that termination resistors (120 Ohm) are correctly installed at both ends of the RS-485 bus.

  5. 5

    5. Temporarily disconnect other devices from the Modbus network to isolate potential conflicts or noisy devices.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

ASFAngle ErrorCFFIncorrect ConfigurationCFI2Configuration Transfer Error
Source: Schneider Electric Altivar Machine ATV320 Variable Speed Drive
View Official PDFSearch more codes in this manual