201515

BICO: Writing to parameter not permitted as the master control is active

Siemens · SINUMERIK 828D

What does 201515 mean?

This alarm occurs when an attempt is made to change the number of Command Data Sets (CDS) or copy from a CDS while the master control is still active. Parameters related to BICO (Bi-directional interconnection) configurations cannot be altered under these conditions to maintain system integrity. This is a functional restriction rather than a critical fault, typically requiring no immediate action as the system prevents an invalid operation.

Common Causes

  • Attempting to change parameters related to Command Data Sets (CDS) or BICO interconnections (e.g., P0800, P0801) while the drive is enabled or running (master control active).
  • Incorrect sequencing in the PLC program: trying to write configuration parameters before placing the drive into a disabled or parameterization-ready state (e.g., P0840=0).
  • Drive operating in a safety-relevant mode (e.g., P9500 active) that prevents dynamic changes to control parameters.
  • An external command (e.g., from a higher-level controller or HMI) is overriding local parameter changes.
  • The 'master control' parameter (e.g., P0840) is configured to a source that is always active, preventing parameter changes.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Before attempting to modify BICO or CDS-related parameters, set the master control to OFF (e.g., P0840 = 0 from PLC or via operator panel).

  2. 2

    2. Ensure the drive is in a safe, disabled state (e.g., main contactor open, STO active if applicable) before attempting parameter changes.

  3. 3

    3. Sequence the PLC program to write these parameters only during initial commissioning or a controlled machine shutdown.

  4. 4

    4. Check for any active safety functions (e.g., STO) that might be preventing parameter writes while active.

  5. 5

    5. If using an engineering tool (e.g., TIA Portal), ensure online parameter changes are allowed, or perform an offline download.

Browse all codes in this manual (37)
Verified technical data. Last updated: April 2026

Related Faults

201590Drive: Motor maintenance interval expired201600SI CU: STOP A initiated206100Infeed: Line supply undervoltage shutdown
Source: Siemens SINUMERIK 828D
View Official PDFSearch more codes in this manual