Siemens · SINUMERIK 828D
This alarm signals that a fault has been detected on a drive connected via PROFIBUS or PROFINET, and its fault memory contents have been reported. The alarm includes specific parameters: the drive identifier (%1), the fault code of the drive (%2), the fault value (%3), and the fault time (%4). This is a general indication of a drive-specific issue; the underlying fault must be diagnosed using the drive's own documentation to prevent process interruptions or damage to the drive.
Click steps to track your progress.
1. Identify the specific drive causing the fault using the drive identifier provided with the alarm, and then check its local display for detailed fault codes.
2. Use the engineering software (e.g., TIA Portal, Step 7) to read the fault buffer of the specified drive for a detailed explanation of its internal fault.
3. Verify the 24VDC control power supply at the drive's control terminals (e.g., X9, X10) using a multimeter.
4. Cross-reference the GSD/GSDML file version in the PLC project with the actual firmware version of the faulty drive's communication module.
5. Monitor the PROFIBUS/PROFINET communication status indicators (e.g., SF, BF LEDs) on the drive to confirm bus activity and data exchange.
6. Perform a drive reset via the engineering software or by cycling the drive's control power after addressing the underlying drive fault.