This alarm signals that the PROFIBUS/PROFINET bus configuration has changed, either due to initial commissioning or the recognition of a new slave/device on the bus. While not an error in itself, the new settings will only become active after a system restart. This requires a controlled restart to ensure the new configuration is properly loaded and the system operates as intended, avoiding potential communication inconsistencies.
Click steps to track your progress.
1. Acknowledge the alarm in the PLC and verify if the reported configuration change corresponds to a planned modification or new device installation.
2. Upload the current hardware configuration from the PLC to the engineering software to compare it with the offline project.
3. If a new device was added, integrate its GSD/GSDML file and configure its parameters in the PLC project, then download the updated configuration.
4. If an existing device's configuration changed, update the relevant parameters in the engineering software (e.g., I/O addresses, module types).
5. Perform a 'Compare' function between the online and offline PLC project to identify the exact differences in the bus configuration.
6. Initiate a complete PLC warm restart (POWER ON/OFF) if a download of the modified configuration requires a full re-initialization of the bus.