Vacon · 20 Compact
The current measurement system has detected an excessive leakage current to ground during startup. This is a strong indication of an insulation failure, either in the motor cables connecting the drive to the motor or within the motor windings themselves.
Click steps to track your progress.
Inspect all motor cables for any signs of damage or compromised insulation.
Perform an insulation resistance test (megger test) on the motor cables and motor windings to ground and between phases, expecting resistance values greater than 1 MΩ.