Vacon · NX Liquid-Cooled Drive
The DC-link voltage has exceeded its predefined limits. This often occurs due to overly short deceleration times during motor stopping, or significant overvoltage spikes originating from the mains supply. For 400-500Vac mains, a fault trips at 911Vdc (warning at 860Vdc); for 500-690Vac mains, a fault trips at 1250Vdc (warning at 1150Vdc). Subcodes S1 (hardware trip) and S2 (overvoltage control supervision) provide additional diagnostic context.
Click steps to track your progress.
Increase the deceleration time parameter in the drive configuration to allow for slower motor braking.
Install a brake chopper and/or brake resistor if not already present, or verify their operation if installed. For INU devices, ensure overvoltage control is set to active.
Measure the incoming AC supply voltage at the drive input terminals to check for transient spikes or sustained high voltage.