Vacon · NX Liquid-Cooled Drive
The current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to ground. This fault is most commonly caused by insulation failure in the motor cables or within the motor windings themselves.
Click steps to track your progress.
Measure the insulation resistance between each motor phase cable (U, V, W) and ground (PE) using a megger.
Measure the insulation resistance between each motor winding (U, V, W) and the motor frame (PE) with a megger.