Vacon · NX Liquid-Cooled Drive
The DC-link voltage has decreased below the predefined limits. This is most often caused by an insufficient supply voltage, a component failure within the drive, a defective input fuse, or an external charge switch that is not properly closed. For 400-500Vac mains, a fault trips at 333Vdc (warning at 371Vdc); for 500-690Vac mains, a fault trips at 573Vdc (warning at 633Vdc). Subcodes S1 (DC-link too low during run), S2 (no data from power unit), and S3 (undervoltage control supervision) are available.
Click steps to track your progress.
If a temporary supply voltage break occurred, reset the fault and restart the drive.
Measure the incoming AC supply voltage at the drive input terminals to verify it meets specified requirements.
Check all input fuses for continuity and proper rating.
Ensure any external charge switch is in the closed position.