3
Earth Fault
Vacon · NX Liquid-Cooled Drive
What does 3 mean?
The current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to ground. This fault is most commonly caused by insulation failure in the motor cables or within the motor windings themselves.
Common Causes
- Insulation failure in motor windings or power cables.
- Ground fault in the connected equipment.
- Moisture or contamination ingress into electrical components.
- Faulty grounding connection.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the insulation resistance between each motor phase cable (U, V, W) and ground (PE) using a megger.
- 2
Measure the insulation resistance between each motor winding (U, V, W) and the motor frame (PE) with a megger.
Verified technical data. Last updated: March 2026
Related Faults
Source: Vacon NX Liquid-Cooled Drive