E-15

SI-F/G Communication Error

Yaskawa · VS-616G5 Variable Speed Drive

What does E-15 mean?

This fault may occur when using the SI-F or SI-G communication options if communication is lost after being established. It signifies a disruption in data exchange with the specific option card (SI-F or SI-G), which can halt control functions or data exchange, leading to operational stoppage and loss of control.

Common Causes

  • Damaged or loose communication cable connected to the SI-F/G option card (e.g., EtherCAT, PROFINET, DeviceNet).
  • Incorrect network configuration (e.g., IP address, subnet mask, device name, scan time) for the SI-F/G card.
  • Faulty SI-F or SI-G communication option card itself.
  • Interference on the communication network (e.g., electromagnetic noise, incorrect grounding).
  • Mismatched firmware versions between the inverter and the SI-F/G card or the master controller.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect physical connections of the communication cable (e.g., RJ45 for EtherCAT/PROFINET) at the SI-F/G card and the network switch/PLC.

  2. 2

    Verify network parameters (e.g., IP address, DeviceNet MAC ID, EtherCAT Node Address) on the SI-F/G card and the master controller.

  3. 3

    Check LED indicators on the SI-F/G card for network status (e.g., LINK/ACT, MS, NS LEDs).

  4. 4

    Temporarily connect the SI-F/G card directly to a configured master controller (PLC/PC) to bypass network infrastructure issues.

  5. 5

    Confirm the firmware version compatibility of the SI-F/G card with the inverter firmware using the inverter's display.

Browse all codes in this manual (34)
Verified technical data. Last updated: April 2026