Yaskawa · VS-616G5 Variable Speed Drive
This fault indicates an external condition has triggered a protective response from the inverter. The specific action taken by the inverter (e.g., ramp to stop, coast to stop, alarm) is determined by parameter F9-03. This is typically activated by an external safety circuit or process interlock.
Click steps to track your progress.
1. Identify the specific external device connected to the inverter's external fault input terminal (e.g., digital input S1, S2).
2. Inspect the status of the identified external fault device (e.g., emergency stop button pushed, overload relay tripped indicator).
3. Measure continuity or voltage at the inverter's external fault input terminal to confirm the signal state (e.g., 24VDC present/absent).
4. Verify the external fault input parameter (e.g., P5-01 for assigned function, P5-02 for normally open/closed logic) is correctly set.
5. Trace the wiring from the external device to the inverter's input terminal for any breaks, loose connections, or unintentional short circuits.