EF0

External Fault

Yaskawa · VS-616G5 Variable Speed Drive

What does EF0 mean?

This fault indicates an external condition has triggered a protective response from the inverter. The specific action taken by the inverter (e.g., ramp to stop, coast to stop, alarm) is determined by parameter F9-03. This is typically activated by an external safety circuit or process interlock.

Common Causes

  • Activation of an external safety device (e.g., emergency stop button, external motor thermal overload relay, pressure switch).
  • Incorrect wiring of the external fault input (e.g., short or open circuit on the terminal block).
  • External fault input parameter (e.g., P5-01 for function, P5-02 for logic) incorrectly configured.
  • Failure of the external device itself, causing a false fault signal.
  • Interference or noise on the external fault input signal line, leading to an unintended trip.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Identify the specific external device connected to the inverter's external fault input terminal (e.g., digital input S1, S2).

  2. 2

    2. Inspect the status of the identified external fault device (e.g., emergency stop button pushed, overload relay tripped indicator).

  3. 3

    3. Measure continuity or voltage at the inverter's external fault input terminal to confirm the signal state (e.g., 24VDC present/absent).

  4. 4

    4. Verify the external fault input parameter (e.g., P5-01 for assigned function, P5-02 for normally open/closed logic) is correctly set.

  5. 5

    5. Trace the wiring from the external device to the inverter's input terminal for any breaks, loose connections, or unintentional short circuits.