Yaskawa · VS-616G5 Variable Speed Drive
This fault indicates that an external protective device or interlock connected to a specific digital input (corresponding to EF4) has been activated, triggering a trip in the inverter. The specific cause depends on the external device wired to that input. This is a safety feature to stop the drive based on external process conditions, preventing damage to the system or injury.
Click steps to track your progress.
Determine which external device corresponds to the EF4 input via control schematics.
Check the status of the external device (e.g., limit switch position, sensor output).
Measure the voltage potential at the inverter's EF4 input terminal (e.g., S4) relative to the common (SC) to confirm input state.
Inspect the wiring path from the external device to the EF4 input for damage or secure connections.
Temporarily disconnect the EF4 input wire from the terminal and measure continuity across the external device's contacts.