Yaskawa · VS-616G5 Variable Speed Drive
This fault indicates that an external protective device or interlock connected to a specific digital input (corresponding to EF7) has been activated, triggering a trip in the inverter. The specific cause depends on the external device wired to that input. This is a safety feature to stop the drive based on external process conditions, preventing damage to the system or injury.
Click steps to track your progress.
Identify the external device (e.g., motor contactor, thermal overload relay) whose auxiliary contact is wired to EF7 (S7).
Check the operational status of the external device; ensure it is energized and not tripped.
Measure the voltage between inverter terminal S7 and SC to confirm the input signal's level.
Inspect wiring integrity from the auxiliary contact to the S7 terminal for breaks, shorts, or loose connections.
Use a multimeter to verify the continuity of the external device's auxiliary contact when it is in its expected non-tripped state.