Traduciendo...
E09

Under-voltage Error

Omron · MX2 Inverter

¿Qué significa E09 ?

This fault occurs when the DC bus voltage inside the inverter drops below a critical threshold, indicating a control circuit fault or an unstable input power supply. This condition can also generate excessive motor heat or cause low torque, leading to an inverter trip to protect the system.

Causas comunes

  • Input AC power supply voltage sag below the inverter's specified minimum operating voltage (e.g., below 340V for 400V class).
  • Loss of one or more phases in the 3-phase AC input supply (e.g., blown fuse, open circuit breaker upstream).
  • Malfunction of the inverter's input rectifier bridge, preventing proper charging of the DC bus capacitors.
  • Heavy transient loads connected to the same power distribution network, causing voltage dips.
  • Internal failure of DC bus capacitors, reducing their energy storage capacity and causing voltage instability.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the input AC voltage across inverter terminals L1, L2, L3 using a multimeter to verify it is within specified range (e.g., 380-480V).

  2. 2

    Check all fuses and circuit breakers in the upstream power supply circuit for the inverter.

  3. 3

    Inspect the input power wiring for loose connections or damage at terminals L1, L2, L3.

  4. 4

    Monitor the DC bus voltage (display parameter d0-02) while the inverter attempts to operate to observe the voltage drop.

  5. 5

    If the problem persists and input voltage is stable, contact service as this may indicate an internal hardware fault (e.g., rectifier, capacitors).

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas