0545
Dead Zone Compensation Parameter Overflow
Fanuc · Alpha i Series Servo Amplifier
What does 0545 mean?
This invalid parameter setting alarm indicates that the internal calculation value of a parameter related to dead zone compensation has overflowed. This typically happens when the compensation setting is too high, leading to mathematical limits being exceeded.
Common Causes
- Dead zone compensation parameter calculation has overflowed.
- Unstable compensation for mechanical dead zones.
- Incorrect settings for dead zone compensation parameters (P04-12).
- Mechanical play impacting control accuracy.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Decrease the setting of the parameter related to dead zone compensation to the extent that the invalid parameter setting alarm is no longer caused.
Verified technical data. Last updated: March 2026
Related Faults
Source: Fanuc Alpha i Series Servo Amplifier