AC frequency too low
Fronius · Primo GEN24
What does 105 mean?
The frequency of the AC grid at the inverter's connection point has dropped below the minimum allowable limit for the Fronius Primo GEN24 208-240 inverter. This condition will cause the inverter to disconnect to prevent damage or improper operation.
Common Causes
- The grid frequency is too low.
- The grid is unstable.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the AC grid frequency at the inverter's connection point using a frequency meter or a multimeter with frequency measurement capability.
- 2
Determine if the low grid frequency is a persistent issue or a transient event.
- 3
Ensure no local large inductive loads are causing significant frequency deviations.
- 4
Immediately contact the grid operator to report the unstable or low grid frequency, as this points to a potential public grid instability or generation issue.