402

No communication with battery

Fronius · Primo GEN24

What does 402 mean?

The Fronius Primo GEN24 208-240 inverter cannot establish communication with the connected battery system. This prevents the inverter from managing battery charging, discharging, and monitoring, rendering the battery inoperable.

Common Causes

  • No communication with the battery.
  • Wiring fault (e.g. incorrect or loose cable, crossed data lines).
  • Battery not powered.
  • Incorrect battery address or settings.
  • Battery system internal fault.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify all communication cables between the Fronius Primo GEN24 208-240 inverter and the battery management system (BMS) are correctly wired and securely connected.

  2. 2

    Ensure the battery system is powered on and its internal status indicators are normal.

  3. 3

    Check the communication settings (e.g., Modbus address, CAN bus settings) in the inverter's user interface to ensure they match the battery system's configuration.

  4. 4

    Inspect the communication cable for physical damage or breaks.

  5. 5

    Perform a power cycle of both the inverter and the battery system to attempt to re-establish communication. Consult the battery manual for proper shutdown/startup procedure.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026