1062

TH. PROTECTION

Kone · Elevator Control

What does 1062 mean?

The motor controller (codes 1062, 2062, 3062) has activated thermal protection. This indicates an over-temperature condition within the controller or its heatsink. The specific lift reaction is controller dependent.

Common Causes

  • Motor controller internal temperature exceeded limits.
  • Insufficient cooling due to blocked ventilation or fan failure.
  • Sustained overload condition leading to excessive heat generation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the control cabinet's ventilation system, cooling fans, and the motor controller's heatsink for dust accumulation, obstructions, or signs of operational malfunction.

  2. 2

    Measure the motor current draw during a lift cycle and compare it against the motor's nameplate data and the controller's configured current limits.

  3. 3

    Verify all motor and drive parameters (e.g., motor nominal current, acceleration/deceleration ramps, current limits) in the Kone Kone Elevator Control system against manufacturer specifications or commissioning records.

  4. 4

    Inspect all power and motor cable connections to the controller for tightness, signs of overheating, discoloration, or corrosion.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults