065
CE4
Lenze · EVF9300 Vector Drive
What does 065 mean?
The controller has entered a BUS-OFF state on the system bus (CAN) due to receiving too many faulty telegrams, leading to disconnection from the bus. This indicates a severe communication breakdown.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify the PE (Protective Earth) connection.
- 4
Check the CAN bus load and reduce the baud rate if necessary, observing cable length limitations.
- 5
Switch off monitoring by setting parameter C0595 = 3.
Source: Lenze EVF9300 Vector Drive