087

Sd7

Lenze · EVF9300 Vector Drive

What does 087 mean?

An initialization error occurred at the absolute value encoder at X8, or the encoder electronics are defective. This can result from a loose cable, an open circuit, an incorrect encoder type, or failure during rotor position adjustment.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check the absolute value encoder for correct function.

  2. 4

    Set the voltage supply via parameter C0421 to 8.0 V.

  3. 5

    If a non-Stegmann encoder is connected, replace it with a compatible Stegmann encoder.

  4. 6

    If a rotor position adjustment failed (C0095 = 1), repeat the adjustment after a TRIP reset and with controller enable.

Source: Lenze EVF9300 Vector Drive
Open Manual (Page 37)