Abnormal Low Pressure (63L Activated)
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
What does UL (100) mean?
The low-pressure switch (63L) is activated, detecting pressure under -0.01MPa [-1.5PSIG] during compressor operation. This indicates either a closed stop valve on the outdoor unit, disconnection or loose connection of the 63L connector or the 63L switch itself, a defective outdoor controller board, refrigerant leakage or shortage, or a malfunction of the linear expansion valve.
Common Causes
- System pressure dropped below the set limit (63L activated).
- Refrigerant leak in the system.
- Low refrigerant charge.
- Clogged indoor unit filter or evaporator.
- Malfunctioning expansion valve.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the stop valve of the outdoor unit to ensure it is open.
- 2
Turn the power off and on again to check if F1 is displayed. If F1 is displayed, follow the F1 processing direction (further details not provided in this manual excerpt).
- 3
Correct the refrigerant amount to the proper level.
- 4
Check the linear expansion valve. Refer to section 10-6.