11001
Connection to device terminated
Kuka · ProfiNet Controller/Device 3.1
Hva betyr 11001 ?
The PROFINET connection to the specified device ({Name}) has been terminated. This fault indicates an interruption in the device's power supply or a physical break in the network connection, leading to a complete loss of communication.
Vanlige årsaker
- The connection to the device has been unexpectedly terminated.
- Network cable disconnected or faulty.
- Device powered off or rebooted unexpectedly.
- Communication protocol error.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the power supply to the PROFINET device {Name} by checking voltage at its power terminals.
- 2
Inspect the network cable connected to device {Name} for any physical damage, loose connections, or disconnections at both ends.
- 3
Check network switch port status connected to device {Name} to confirm link activity.