Connection between PLC and device could not be established
Kuka · ProfiNet Controller/Device 3.1
Hva betyr 11006 ?
The PROFINET connection between the PLC and the specified device ({Name}) could not be established within the configured timeout period. This can be caused by an excessively low bus timeout setting, a mismatch between the controller and PLC configurations, or a defective PROFINET device, preventing proper operation.
Vanlige årsaker
- A connection could not be established between the PLC and the device.
- Incorrect IP address, subnet mask, or port configuration.
- Network infrastructure issues or firewall blocking communication.
- Device not powered on or not accessible on the network.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Increase the 'Bus timeout' parameter setting in the PROFINET configuration on the robot controller (refer to Page 18) to allow more time for connection.
- 2
Verify that the PROFINET device configuration in WorkVisual on the robot controller matches the PROFINET configuration loaded in the PLC for device {Name}.
- 3
Perform diagnostics on the PROFINET device {Name} itself, potentially replacing it if internal faults are detected.