Configured device differs from real device

Kuka · ProfiNet Controller/Device 3.1

Hva betyr 11007 ?

The PROFINET device configured in the controller's software does not match the actual physical device connected at the specified Slot and Subslot for {Name}. This configuration discrepancy prevents correct communication and operation of the device.

Vanlige årsaker

  • The configured device parameters do not match the actual device.
  • Configuration file loaded into the PLC is for a different hardware model or revision.
  • Device has been replaced or its configuration changed without updating the PLC.
  • Incorrect device identification during network scan.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Compare the configured device type and model in WorkVisual for device {Name} at Slot {Slot}, Subslot {Subslot} with the actual device nameplate information.

  2. 2

    Update the PROFINET configuration in WorkVisual to precisely match the physically connected device's identity at the specified slot and subslot.

  3. 3

    Ensure the GSDML file used for device {Name} in the PROFINET project is the correct version for the installed hardware.