05430000 hex

ESC Error

Omron · NJ/NX-series Machine Automation Controller

What does 05430000 hex mean?

An error occurred in the EtherCAT slave communications controller. This fault indicates a problem with the EtherCAT communication interface on the slave device, potentially leading to loss of control or data exchange.

Common Causes

  • Error of the EtherCAT slave communications controller or false detection when the AL status code is 0051 hex
  • Error access from the non-OMRON EtherCAT master when the AL status code is 0050 hex

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect EtherCAT communication cables for damage, proper routing, and secure connections at both the Omron NJ/NX controller and the affected slave device.

  2. 2

    Verify the auxiliary power supply voltage to the affected EtherCAT slave device against its specified nominal voltage.

  3. 3

    Check the status LEDs on the affected EtherCAT slave device for any error indications, referencing the device's manual for interpretation.

  4. 4

    Verify the EtherCAT network configuration parameters (e.g., slave address, topology, cycle time) in the Omron Sysmac Studio project match the actual physical setup and slave device specifications.

Browse all codes in this manual (96)
Verified technical data. Last updated: March 2026