Phase-Z Connection Error
Omron · NJ/NX-series Machine Automation Controller
What does 08160000 hex mean?
An error such as broken wiring was detected in the external encoder phase-Z connection. This indicates a physical wiring issue with the external encoder's Z-phase signal, impacting its reference position detection.
Common Causes
- An error such as broken wiring was detected in the external encoder phase-Z connection.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Inspect the entire cable run between the external encoder and the Omron NJ/NX controller for physical damage, wear, and proper termination at both ends.
- 2
Verify the continuity of the Z-phase signal wire, its return path, and shield (if applicable) using a multimeter between the encoder connector and the Omron NJ/NX controller's input terminals.
- 3
Measure the supply voltage at the external encoder's power input terminals to confirm it meets the manufacturer's specified voltage range.
- 4
Check the encoder input parameters within the Omron NJ/NX controller's Sysmac Studio software, ensuring correct Z-phase input settings and encoder type configuration.
- 5
Monitor the Z-phase input status in the Omron NJ/NX controller's diagnostic tools (e.g., I/O monitor) while slowly rotating the encoder to confirm signal detection.