08410000 hex

Overvoltage Error

Omron · NJ/NX-series Machine Automation Controller

What does 08410000 hex mean?

The main circuit power supply voltage (P-N voltage) exceeded the operation guarantee range. This indicates an unsafe voltage level in the main power circuit, which can damage components.

Common Causes

  • The P-N voltage exceeded the specified value
  • The input voltage increased
  • The Regeneration Resistor wiring is broken
  • The External Regeneration Resistor is set or selected inappropriately
  • Servo Drive failure

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the incoming AC supply voltage at the main circuit power terminals of the Omron controller and compare it to the specified nominal voltage range.

  2. 2

    Inspect all main circuit power wiring and connections for looseness, corrosion, or damage that could lead to voltage instability.

  3. 3

    Verify the proper operation of upstream surge protection devices (SPDs) and line filters to mitigate potential transient overvoltage events.

  4. 4

    Check the Omron controller's configured power supply monitoring parameters and input voltage thresholds to ensure they align with the actual installation and manufacturer specifications.

Browse all codes in this manual (96)