A10101
Synchronous Input Data Refresh Error
Omron · SYSMAC CJ2 CPU Unit
What does A10101 mean?
This word (A10101) will contain the value '0001 hex' when the CPU Unit fails to receive synchronous input data from a Synchronous Unit within the specified time window. This indicates a loss of synchronization or communication with the connected unit. A value of '0000 hex' indicates normal operation.
Common Causes
- Failure of the CPU Unit to receive synchronous input data from a Synchronous Unit.
- Synchronous input data not transmitted or received within the configured synchronous operation cycle time.
- Disrupted communication link or physical connection issues between the CPU and the Synchronous Unit.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the communication link and physical connections between the CPU Unit and the Synchronous Unit for integrity.
- 2
Check the synchronous operation cycle time setting in the PLC Setup (A10102) to ensure it is adequate for reliable data reception.
- 3
Confirm that the Synchronous Unit is transmitting data correctly and within the expected timing parameters.
Verified technical data. Last updated: March 2026
Related Faults
Source: Omron SYSMAC CJ2 CPU Unit