A408.00 to A408.07

Basic I/O Unit Error - Slot Number

Omron · SYSMAC CJ2 CPU Unit

What does A408.00 to A408.07 mean?

When an error occurs in a Basic I/O Unit, this word stores the slot number (00 to 09 hexadecimal) where the error was detected. The CPU Unit continues operating, but the ERR/ALM indicator on the front of the CPU Unit will flash. The presence of this error is also indicated by A402.12 being ON.

Common Causes

  • Hardware malfunction within a Basic I/O Unit located in the indicated slot
  • Improper seating or connection of the I/O Unit in its slot
  • Internal fault within the Basic I/O Unit itself

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the problematic Basic I/O Unit by checking the slot number indicated in A408.00 to A408.07

  2. 2

    Visually inspect the identified I/O Unit for any physical damage or loose connections

  3. 3

    Re-seat the Basic I/O Unit firmly into its slot

  4. 4

    Replace the Basic I/O Unit if visual inspection or re-seating does not clear the error