A528.05

RS-232C Port Timeout Error

Omron · SYSMAC CJ2 CPU Unit

What does A528.05 mean?

This flag turns ON when a timeout error occurs during RS-232C communication. This indicates that a response from the connected device was not received within the expected timeframe after a transmission. This error is valid in Serial Gateway mode, NT Link mode, and for both Polling and Polled Units in Serial PLC Link Mode.

Common Causes

  • The connected device is not responding or is offline
  • Communication cable issues (disconnection, damage)
  • Incorrect communication protocol or addressing settings
  • Timeout parameter set too short for network latency or device response time

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the connected device is powered ON and operating correctly

  2. 2

    Inspect the RS-232C cable for continuity and proper connection at both ends

  3. 3

    Check communication parameters, including device address and protocol settings, on both the PLC and the connected device

  4. 4

    Adjust the communication timeout parameter in the PLC configuration if the connected device has a slower response time

  5. 5

    Restart the RS-232C port by turning ON the Serial Port Restart Bit (A526.00) from OFF to ON

Browse all codes in this manual (27)
Verified technical data. Last updated: March 2026

Related Faults

Omron Error A528.05: RS-232C Port Timeout Error — Troubleshooting Guide | ErrorLib