Special I/O Unit Setting Error
Omron · SYSMAC CJ2 CPU Unit
What does A402.02 mean?
This fault indicates a setting error for a Special I/O Unit. When a Special I/O Unit Setting Error occurs, A402.02 and the bit in A428 to A433 corresponding to the Unit's unit number (0-95) are turned ON. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash. These flags are refreshed when power is turned ON or I/O is recognized.
Common Causes
- Incorrect configuration parameters or settings for a Special I/O Unit (e.g., I/O table, PLC Setup).
- Mismatched hardware or software settings for the Special I/O Unit.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Identify the specific Special I/O Unit with the setting error by checking bits A428.00 to A433.15.
- 2
Compare the configured settings for the identified Special I/O Unit in the CX-Programmer with the actual hardware.
- 3
Reconfigure the Special I/O Unit settings to match the expected parameters.
- 4
Cycle power or re-recognize I/O to refresh the status after correcting settings.