413

FIELD CURRENT TRACKING FAULT

Otis · DSD 412 Elevator System

What does 413 mean?

The actual field current failed to track the field current command by more than F192 (Default = 0.05) for 5 seconds. This condition is a warning and is not a shutdown fault.

Common Causes

  • Incorrect AC voltage on AC1 and AC2.
  • Incorrect self-tune values and/or incorrect field response settings.
  • Parameter F192 ('F413 Detection Level') set too low.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check AC voltage on AC1 and AC2; typically expect 1.5 to 2.5 times VAC(min), where VACmin = VDC/0.9 or (Full Fld Amps * Field resistance)/0.9.

  2. 2

    Verify the drive's self-tune values and field response settings.

  3. 3

    Monitor parameter F620 Fld Trkg Diff; it should remain less than F192.

  4. 4

    Consider increasing parameter F192 ('F413 Detection Level') to eliminate this warning, but exercise caution.

Browse all codes in this manual (57)
Verified technical data. Last updated: March 2026

Related Faults

Source: Otis DSD 412 Elevator System