Motor overload
Schindler · Easy Altivar ATV310 Drive
What does F013 mean?
The drive displays an F013 fault when the Motor thermal state (808) exceeds 118%. This indicates that the motor is operating beyond its safe thermal limits, risking damage to the motor windings.
Common Causes
- The motor's thermal state (808) has exceeded 118% of its rated thermal capacity.
- Excessive mechanical load on the motor, leading to higher than normal current draw.
- Insufficient cooling for the motor, such as blocked ventilation fins or a malfunctioning motor fan.
- Incorrect motor nameplate data or overload protection parameters configured in the drive.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Reduce the mechanical load on the motor to bring its operating current within safe limits.
- 2
Check the motor's cooling system for proper operation, clear any obstructions from cooling fins, and ensure adequate airflow around the motor.
- 3
Monitor the Motor thermal state (808) parameter in the Monitoring mode (MOn) to observe the motor's thermal condition.
- 4
Verify that all motor parameters in the drive (e.g., motor nominal current, motor overload curve) accurately match the motor's nameplate data.
- 5
Allow the motor to cool down before attempting to restart the drive.