HISUC
High Suction Pressure
Yaskawa · iQpump1000 AC Drive
What does HISUC mean?
The suction pressure has risen above the level set in Q5-12 for longer than the time set in Q5-13. This fault is effective only when Q5-14 (High Suction Pressure Behavior Select) is set to 2 (fault).
Common Causes
- System suction pressure is too high, exceeding the Q5-12 threshold for the Q5-13 duration.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Reduce the system pressure.
- 2
Set the High Suction Pressure fault characteristics using parameters Q5-12, Q5-13, and Q5-18.
- 3
Control drive response to this condition using Q5-14 (High Suction Pressure Behavior Select).
- 4
Control auto-restart of this fault using Q5-14 (High Suction Pressure Behavior Select) and Q5-15 (Suction Pressure Auto-restart Time).
Verified technical data. Last updated: March 2026
Related Faults
Source: Yaskawa iQpump1000 AC Drive