ACS880 · Primary Control Program Firmware
The Safe Torque Off (STO) function has been activated, removing power from the motor and preventing unintended starts. This fault indicates that the STO safety chain has been interrupted or a fault related to STO occurred, regardless of whether one or both signals were lost.
Click steps to track your progress.
Verify that all external safety devices (e.g., emergency stop buttons, safety gates, safety relays) in the STO circuit are in their safe operating state and not activated.
Check the STO input signals (typically digital inputs for STO1 and STO2) at the drive terminals for proper voltage levels (e.g., 24VDC when safe torque off is inactive).
Inspect the wiring of the STO safety chain for any breaks, loose connections, short circuits, or damage.
If applicable, test the functionality of external safety devices connected to the STO inputs to ensure they are operating correctly.
Refer to the drive's hardware manual for detailed information on STO wiring, signal specifications, and diagnostic indicators.