71A5

Mechanical brake opening not allowed

ACS880 · Primary Control Program Firmware

What does 71A5 mean?

The ACS880 drive detected that the conditions required for the mechanical brake to open cannot be fulfilled. This can be caused, for example, if the brake has been prevented from opening by parameter 44.11 Keep brake closed.

Common Causes

  • Parameter 44.11 Keep brake closed is set to 'Always' or 'When stopped', preventing the brake from opening unintentionally.
  • Incorrect configuration of other open conditions or interlocks in parameter group 44 Mechanical brake control.
  • The brake acknowledgement signal (if used) does not match the expected brake status, indicating it's still closed or stuck.
  • External safety interlocks or process conditions are not met, which inhibits brake opening.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check parameter 44.11 Keep brake closed in parameter group 44 Mechanical brake control and ensure it is not preventing brake opening unintentionally.

  2. 2

    Review other parameters in group 44 related to brake opening conditions, delays, and interlocks to confirm correct configuration.

  3. 3

    Verify that the acknowledgement signal (if used) correctly reflects the actual status of the brake (i.e., it should indicate 'open' when commanded).

  4. 4

    Ensure that all safety conditions or external interlocks allowing brake opening are met (e.g., motor rotating, sufficient motor torque).

  5. 5

    If necessary, manually inspect the brake to ensure it is not mechanically jammed and can physically open.