A2B3

Earth leakage

ACS880 · Primary Control Program Firmware

What does A2B3 mean?

The ACS880 drive detected an earth fault or current unbalance in the motor or the motor cable. This indicates a leakage current to ground, which can be a safety hazard or damage equipment, generating a warning.

Common Causes

  • Insulation failure in the motor power cable, allowing current to flow to ground.
  • Motor winding insulation breakdown due to age, moisture, or overheating.
  • Moisture, dirt, or contaminants in motor or cable terminal connections causing a leakage path.
  • Incorrect setting of parameter 31.20 Earth fault, where the drive is configured to generate a 'Warning' for this condition.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Immediately de-energize and lock out the drive before performing checks.

  2. 2

    Inspect the motor power cables for visible damage to insulation, especially where they enter conduit or motor terminal boxes.

  3. 3

    Check the motor terminal box for moisture, dirt, or loose connections that could create a leakage path.

  4. 4

    Measure insulation resistance between each motor phase and ground, and between phases, using a megger (e.g., 500VDC) to identify potential earth faults (expect >1MΩ).

  5. 5

    Verify parameter 31.20 Earth fault is set appropriately for the application (e.g., 'Warning' for monitoring or 'Fault' for tripping on severe conditions).