ACS880 · Primary Control Program Firmware
This is a programmable warning related to the DC charging circuit of the drive. It is typically triggered by a timer or counter indicating an anomaly or exceeding a threshold during the DC bus pre-charge sequence.
Click steps to track your progress.
Check the event log for an auxiliary code or specific counter/timer responsible for this warning.
Review parameters related to DC bus charging supervision and thresholds.
Verify the incoming AC supply voltage is within specifications for the drive, ensuring adequate power for pre-charge.
Inspect DC bus pre-charge resistors and contactors for proper operation, damage, or degradation.
Ensure the pre-charge sequence completes within the expected timeframe.