ACS880 · Primary Control Program Firmware
An external fault condition, sourced from a configurable input (parameter 31.01 External event 1 source), has been detected by the ACS880 drive. This fault indicates an issue originating from an external device or safety system.
Click steps to track your progress.
Check parameter 31.01 External event 1 source to identify the specific digital input or source triggering this fault (e.g., DI1, DI2).
Inspect the external device or system connected to the identified input for its fault condition (e.g., press the reset on an overload relay, check E-stop status).
Verify the wiring and connection integrity of the external fault signal from the device to the drive's digital input terminals.
Measure the state of the external fault signal (voltage) at the drive's input terminals to confirm it is open or closed as expected.
Clear the external fault condition at its source and then reset the drive.