External fault 1

External fault 1

ACS880 · Primary Control Program Firmware

What does External fault 1 mean?

An external fault condition, sourced from a configurable input (parameter 31.01 External event 1 source), has been detected by the ACS880 drive. This fault indicates an issue originating from an external device or safety system.

Common Causes

  • The external signal configured in parameter 31.01 External event 1 source has changed state, indicating a fault condition from an external device (e.g., thermal overload relay, emergency stop, safety gate switch, auxiliary contact).
  • Broken wire or loose connection in the external fault signal wiring to the drive's digital input.
  • Malfunction or improper operation of the external device sending the fault signal.
  • Incorrect configuration of the digital input (e.g., normally open vs. normally closed) for the external fault signal.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check parameter 31.01 External event 1 source to identify the specific digital input or source triggering this fault (e.g., DI1, DI2).

  2. 2

    Inspect the external device or system connected to the identified input for its fault condition (e.g., press the reset on an overload relay, check E-stop status).

  3. 3

    Verify the wiring and connection integrity of the external fault signal from the device to the drive's digital input terminals.

  4. 4

    Measure the state of the external fault signal (voltage) at the drive's input terminals to confirm it is open or closed as expected.

  5. 5

    Clear the external fault condition at its source and then reset the drive.

Browse all codes in this manual (56)
Verified technical data. Last updated: April 2026

Related Faults

2330Earth leakage3130Input phase loss3181Cross connection
Source: ACS880 Primary Control Program Firmware
Open Manual (Page 147)Search more codes in this manual