FA82

Safe torque off 2

ACS880 · Primary Control Program Firmware

What does FA82 mean?

Loss of one of the Safe Torque Off (STO) signals (STO2). This fault indicates an issue with the second channel of the dual-channel STO safety circuit, causing the drive to enter a safe state by removing motor torque.

Common Causes

  • Interruption or wiring fault in the STO2 signal path from the safety device to the drive.
  • Fault within the external safety device connected to STO2 (e.g., safety relay output failure, E-stop contact issue).
  • Internal STO circuit fault affecting only the STO2 channel.
  • Parameter 31.22 STO diagnostics is set to detect single-channel loss as a fault (when running) or a fault/warning (when stopped).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the specific STO2 input signal at the drive terminal for correct voltage level (e.g., 24VDC when safe torque off is inactive).

  2. 2

    Inspect the wiring for the STO2 channel from the safety device to the drive for breaks, loose connections, or damage.

  3. 3

    Check the external safety device connected to the STO2 channel for proper operation and reset if necessary.

  4. 4

    Ensure parameter 31.22 STO diagnostics is set appropriately; 'Fault' or 'Warning' mode will react to single-channel loss.

  5. 5

    Consult the drive's hardware manual for STO wiring diagrams and signal specifications to confirm correct installation.