Fronius · Primo GEN24
The Fronius Primo GEN24 208-240 inverter has detected that the connected grid type is not supported or that no AC grid is connected. This prevents the inverter from synchronizing and feeding power.
Click steps to track your progress.
Verify that the AC grid is correctly connected to the Fronius Primo GEN24 208-240 inverter's AC terminals and all connections are secure.
Confirm that the grid type (e.g., single-phase, split-phase) configured in the inverter settings matches the actual grid connection.
Check if the AC output breaker or disconnect switch for the inverter is closed and not tripped.
Ensure the correct country/grid standard is selected in the inverter's configuration settings.
Measure the AC voltage at the inverter's AC input terminals to confirm the grid is present and within specified voltage limits.