EL
ErrorLib
Brands
||
  1. Home
  2. Fronius
  3. Primo GEN24
  4. 301
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

301

Insulation fault on PV generator (PV1)

Fronius · Primo GEN24

What does 301 mean?

The Fronius Primo GEN24 208-240 inverter has detected an insulation fault (ground fault) on the PV generator (PV1 string). This means there is an unintended electrical path between the PV array's DC conductors and ground, posing a safety risk and preventing power production.

Common Causes

  • Insulation fault on PV generator (PV1).
  • Water ingress into PV modules or junction boxes.
  • Damaged PV cable insulation (e.g., rodent damage, mechanical stress).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Safely disconnect the PV array (PV1) from the Fronius Primo GEN24 208-240 inverter using the DC disconnector and AC breaker.

  2. 2

    Using a megohmmeter (insulation resistance tester), measure the insulation resistance of the PV1 string to ground (PV+ to ground, PV- to ground) - expect >1 MΩ.

  3. 3

    Visually inspect all PV modules, cables, and connectors for the PV1 string for any signs of damage, moisture ingress, or degradation.

  4. 4

    Check all junction boxes and combiner boxes for moisture, corrosion, or loose connections.

  5. 5

    If the fault persists, isolate individual PV modules or sections of the PV1 string to pinpoint the exact location of the insulation fault.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

102AC voltage too high103AC voltage too low1030WSD Open
Source: Fronius Primo GEN24
Open Manual (Page 149)Search more codes in this manual