Fronius · Primo GEN24
The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing from the PV2 string on the DC side. This suggests a potential short circuit within the PV2 array or an improper string configuration.
Click steps to track your progress.
Disconnect the PV2 string using the DC disconnector and visually inspect all PV modules, wiring, and connectors for any damage or indications of a short circuit.
Measure the open-circuit voltage (Voc) and short-circuit current (Isc) of the PV2 string and compare them against expected values from the module datasheet.
Confirm that the PV2 string configuration (number of modules in series and parallel) adheres to the Fronius Primo GEN24 208-240 inverter's maximum DC current specifications.
Inspect any external DC combiner box or array wiring associated with PV2 for potential short circuit conditions.
If external components are confirmed good, the fault might be internal to the inverter; contact Fronius service.