SEW Eurodrive · MOVIDRIVE system
The signal level from Encoder 1 is too low, falling below the permitted limit during monitoring. This indicates a problem with the wiring, external electromagnetic interference (EMC), or a faulty encoder, leading to unreliable position feedback.
Click steps to track your progress.
Measure the voltage levels of Encoder 1's differential signals (e.g., A+ to A-, B+ to B-) at the drive's encoder input terminals (e.g., X11) using an oscilloscope.
Check the continuity and resistance of each conductor in the Encoder 1 cable from the encoder to the drive.
Verify Encoder 1's supply voltage (e.g., 5VDC or 24VDC) at the encoder terminals.
Ensure the cable shielding is properly grounded at both ends or as recommended by the manufacturer.
Confirm the correct termination resistance (e.g., P6-05 setting) is selected in the drive's parameters for the specific encoder type.