EL
ErrorLib
Brands
||
  1. Home
  2. SEW Eurodrive
  3. MOVIDRIVE system
  4. F14.21
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F14.21

SSI error bit

SEW Eurodrive · MOVIDRIVE system

What does F14.21 mean?

An error bit has been set in the SSI protocol by Encoder 2, indicating a data or communication problem. This can result from incorrect startup parameters, encoder settings, wiring issues, or external interference, affecting position feedback reliability.

Common Causes

  • Mismatch between the SSI resolution (P3-55) or number of turns (P3-56) configured in the drive for Encoder 2 and the actual encoder specifications.
  • Intermittent electrical noise on the SSI data or clock lines, potentially due to inductive loads or unshielded cables running parallel to power cables.
  • Minor internal malfunction within Encoder 2, causing occasional setting of non-critical error bits in the SSI telegram.
  • Ground loop issues affecting the SSI signal integrity, potentially caused by multiple grounding points or incorrect earthing practices.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Cross-reference drive parameters P3-55 (SSI resolution for Encoder 2) and P3-56 (SSI number of turns for Encoder 2) against the Encoder 2 datasheet and adjust if necessary.

  2. 2

    Visually inspect the routing of the Encoder 2 cable to ensure it is separated from high-current power cables and that shielding is continuous.

  3. 3

    Capture SSI clock and data signals at drive terminal X2 using an oscilloscope to identify any transient noise or signal distortions.

  4. 4

    Perform a resistance check on all SSI signal lines (CLOCK+, CLOCK-, DATA+, DATA-) and ground connection from drive terminal X2 to encoder connector.

  5. 5

    Reset the Encoder 2 configuration parameters in the drive (e.g., P3-50 to default) and reconfigure carefully.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

12.1Brake Output Fault12.224V Brake Voltage Fault13.1Position Comparison Check (Encoder 1)
Source: SEW Eurodrive MOVIDRIVE system
View Official PDFSearch more codes in this manual