F14.22

Internal fault – critical

SEW Eurodrive · MOVIDRIVE system

What does F14.22 mean?

Encoder 2 is signaling a critical internal fault, meaning the encoder itself has detected a severe malfunction. This prevents the drive from receiving reliable position feedback and could lead to unsafe or uncontrolled operation.

Common Causes

  • Catastrophic hardware failure within Encoder 2, such as a damaged ASIC or optical sensor array.
  • Complete loss of internal power regulation within Encoder 2, rendering the encoder inoperable and signaling a critical fault.
  • Severe mechanical damage to Encoder 2 (e.g., bearing failure, shaft misalignment) causing internal sensor disruption.
  • Persistent over-temperature condition within Encoder 2 exceeding its operational limits (e.g., >85°C) due to ambient conditions or internal failure.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the supply voltage to Encoder 2 at the encoder terminals (e.g., +10VDC or +24VDC) is within the specified tolerance.

  2. 2

    Check the encoder housing for signs of physical damage, overheating (discoloration), or excessive vibration during operation.

  3. 3

    Disconnect Encoder 2 and measure the resistance across its internal power supply pins (e.g., +V to 0V) to detect a short circuit.

  4. 4

    Log any associated drive alarms (e.g., overcurrent or motor overload) that might indicate a secondary issue stressing the encoder.

  5. 5

    As this is a critical internal fault, replace Encoder 2 with an identical, known-good unit for immediate troubleshooting.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

12.1Brake Output Fault12.224V Brake Voltage Fault13.1Position Comparison Check (Encoder 1)
Source: SEW Eurodrive MOVIDRIVE system
View Official PDFSearch more codes in this manual